Cerberus Pyrotronics DI-3 Ionization Smoke Detector

$450.00
Availability:
1 in stock
Warranty:
90 Days
Condition:
New
Quantity:
- +

Product Description

The Siemens Cerberus Pyrotronics DI-3 is a conventional plug-in Ionization Smoke Detector.

COMPATIBLE BASES
DB-3S Standard Low-profile Mounting Base
ADB-3 Audible Base
Please note: All parts should be installed and tested by a certified fire alarm company.

Questions (4)

What are the electrical specifications for this product?
Answer:
Current Requirements: Normal — 100uA (350uA peak surge upon application of power) Alarm — 80mA
Voltage Range: 21 +3 VDC
Operating Temperature: +32°F (0°C) to +100°F (38°C) per UL
Humidity: 0-93% Relative Humidity
Air Velocity: 0-300 ft./min. Model DI-3 0-1200 ft./min.
What is the wiring requirements for this product?
Answer:
The detector, or group of detectors, shall require a two-wire circuit of #18 AWG thermoplastic fixture wire enclosed in conduit, or #18 AWG limited energy shielded cable without conduit, if permitted by local codes.
What if I need to return this?
Answer:
All products are covered by our 90-day warranty and come with a prepaid UPS return label and RMA form. Returning products has never been this easy.
What if I need support?
Answer:
Our friendly team is on hand with expert advice and assistance. Contact us Mon-Fri 8am-8pm by phone (888.303.2656), by email (support@buyfirealarmparts.com) or using our online chat. Responses within 1 business day (if not sooner!)