Fire-Lite MMF-300-10 Ten-Input Monitor Module
$875.00
The Fire-Lite MMF-300-10 is an intelligent addressable ten-input monitor module that interfaces a compatible Fire-Lite control panel with normally open dry-contact devices such as pull stations, security contacts, and flow switches. It provides ten addressable Class B circuits or five addressable Class A circuits, uses one starting address with the next nine points assigned automatically, and allows up to two unused addresses to be disabled.
Key Specifications:
Type: Intelligent addressable ten-input monitor module
Core Function(s): Independently monitors multiple dry-contact initiating circuits and reports normal, open, or short status back to the panel
Loop/Protocol: Fire-Lite SLC
Power: 3.5 mA standby current with all addresses used; 55 mA alarm current with all ten LEDs on
Indicators/UI: Panel-controlled green LED indicators for each point; LEDs can blink, latch on, or latch off
Circuit Configuration: Ten addressable Class B IDCs or five addressable Class A IDCs
Addressing: Starting address set from 01 to 150; remaining nine addresses are assigned automatically; up to two unused addresses may be disabled
IDC Ratings: 1500 Ohms maximum IDC wiring resistance; 10.2 VDC maximum IDC voltage; 240 uA maximum IDC current
Wiring: 12 to 18 AWG removable plug-in terminal blocks
Mounting: Mounts in a CHS-6 chassis, BB-6F cabinet, or BB-2F cabinet
Dimensions: 6.8 inches H x 5.8 inches W x 1.25 inches D
Environmental: 32 F to 120 F; 10% to 85% non-condensing
Compatible Accessories:
CHS-6 - Chassis for mounting up to six modules
BB-6F - Cabinet for up to six modules on a CHS-6 chassis
BB-2F - Cabinet for one or two modules
System Compatibility:
Compatible with Fire-Lite intelligent control panels that support SLC monitor modules