Gamewell FCI CZI-95 Addressable Conventional Zone Interface

$220.00

Availability

Out of Stock

Condition

New

Warranty

90 Days
The Gamewell FCI CZI-95 is an addressable conventional zone interface for 600 Series and ILI95-E3 Series analog addressable fire alarm control panels. It connects the panel analog circuit to a supervised conventional zone, supporting normally open contact devices or up to 25 conventional smoke detectors. Key Specifications: Type: Addressable conventional zone interface module Core Function(s): Monitors a supervised conventional zone for normally open dry-contact devices or compatible conventional smoke detectors Loop/Protocol: XP95 protocol compatible; connects to compatible Gamewell-FCI analog addressable circuits Power: 0.010A standby current; 0.102A maximum alarm current Indicators/UI: Built-in LED for local alarm annunciation and device status Circuit Configuration: Supports Style B, C, D, or E wiring Device Support: Monitors up to 25 conventional smoke detectors through a three-wire circuit Programming: Field programmable using a single onboard DIP switch Mounting: Surface or flush mount using a standard double-gang electrical backbox Zone Features: Supports ANDing Type Zones and cross-zoning Compatible Accessories: 70839 - Trim ring for flush mounting System Compatibility: Compatible with Gamewell-FCI 600 Series and ILI95-E3 Series analog addressable fire alarm control panels. Each analog circuit supports up to 40 CZI-95 modules; IF610 supports up to 40 total per system.