Silent Knight IDP-ZONE-6 Six Zone Interface Module
$500.00
The Silent Knight IDP-ZONE-6 is an addressable six-zone two-wire interface module for Silent Knight IFP-series fire alarm control panels that lets one panel monitor up to six independent zones of compatible conventional two-wire smoke detectors. It is built for retrofit applications, supervises both the detector circuits and the external power supply, and allows up to two unused inputs to be disabled.
Key Specifications:
Type: Addressable six-zone two-wire interface module
Core Function(s): Interfaces and monitors up to six zones of compatible conventional two-wire smoke detectors
Loop/Protocol: SLC
Power: 15 to 32 VDC operating voltage; 2 mA standby current; 40 mA maximum alarm current assuming all six LEDs are on
Indicators/UI: Individual LED indication for each zone input
Circuit Configuration: Supports Class B and Class A wiring
Addressing: Rotary address switches; up to two unused inputs can be disabled
IDC Ratings: Supervised, power-limited initiating device circuits; 25 Ohms maximum IDC wiring resistance; 3.9K Ohm end-of-line resistance
External Power Supply: 50 mA standby current; 270 mA alarm current
Mounting: Mounts in an IDP-ACB cabinet, which can house one or two IDP-ZONE-6 modules
Physical: 6.8 inches H x 5.8 inches W x 1.25 inches D
Environmental: 32 F to 120 F; 10% to 93% non-condensing
Compatible Accessories:
IDP-ACB - Cabinet for one or two IDP-ZONE-6 modules
System Compatibility: Silent Knight IFP-series fire alarm control panels that support IDP addressable modules