Mircom FA-204 (4-Zone FACP) Replacement Board
$425.00
This is the replacement board for the Mircom FA-204 (4-Zone FACP).
FEATURES and SPECIFICATIONS
— Four supervised Style B (Class B) or 2 Style D (Class A) initiating circuits; configurable. [Compatibility ID “A”]
Power limited:26VDC, 3 mA standby, 1.5Vp-p ripple, 50 mA max. (alarm)
— Two Class A/B (Style Y/ Z) indicating circuits; configurable as strobes or audibles.
Power limited:24 VDC unfiltered
— 1.7 A @ 49°C per circuit (5A total)
— One (DM-204) Zone Adder Module may be added.
— Initiating circuit disconnect switches.
— Optional DACT (DACT-100A) or city tie adder module (PR-100).
— Optional RM-204 / RM-208 Relay Module.
— Resettable four-wire smoke supply.
Power limited: 28VDC, 100mA max, 1.5Vp-p ripple
— Aux power supply.
— Power limited: 24VDC, 300mA max, unfiltered
— for RTI or Remote Annunciators
— 1 RS-485 connection for up to 3 RAM-208 Remote Annunciators.
— 1 RTI interface for connection to an RTI Remote Trouble Indicator.