Silent Knight 6808 Intelligent Addressable FACP
$1,500.00
The 6808 is an intelligent addressable fire alarm control panel with a built-in dual-path communicator. One on-board SLC supports up to 99 SK detectors and 99 SK modules (198 addresses total) or 127 SD devices, and the panel links up to 17 panels for single-point communications. Four Flexput circuits can be configured as NACs or auxiliary power, and a USB port enables fast programming. A supervised 4-line LCD, two programmable Form C relays, a dedicated trouble relay, and features like JumpStart auto-programming streamline setup and service.
NOTE: The Silent Knight 6808 is a direct replacement for the 5808.
Key Specifications:
Type: Intelligent addressable FACP with built-in communicator
SLC Capacity: 198 SK addresses (99 detectors + 99 modules) or 127 SD devices (one on-board SLC)
I/O & Synchronization: Four Flexput circuits (3 A max per circuit; 6 A system total); selectable sync for Amseco, System Sensor, Wheelock, and Gentex appliances
Communications: Built-in DACT supporting IP and POTS reporting; optional cellular
Programming & Ports: Built-in USB for PC programming; RS-485 SBUS for accessories
System Design Aids: JumpStart auto-programming; 250 software zones and 250 output groups; supports up to 20 SBUS devices
Networking: Link up to 17 panels over copper or fiber for single-point communications
Power Supply / Charging: 6 A total across Flexput outputs; battery charging capacity 17–55 Ah; cabinet holds two 18 Ah batteries
Primary Power: 120 VAC, 60 Hz, 3.3 A
Compatible Modules & Accessories:
5860 – LCD remote annunciator (gray)
5860R – LCD remote annunciator (red)
6860 – 4×40 LCD remote annunciator (red)
6855 – LCD remote annunciator (red)
5880 – LED I/O module
5883 – 10-relay interface board
5824 – Serial/parallel printer interface
5895XL – 6 A auxiliary power module with Flexput
5496 – 6 A NAC power expander
Compatible Detectors & Devices:
SK-PHOTO-W – Photoelectric smoke
SK-PHOTO-T-W – Photoelectric + heat
SK-HEAT-W – Fixed-temperature heat
SK-HEAT-ROR-W – Rate-of-rise heat
Also compatible with SD-series (Hochiki protocol) detectors and modules when the panel is programmed for SD devices. SK and SD cannot be mixed on the same system.
Compatible for use with: