Kidde FX-64R (Intelligent FACP)
$950.00
The Kidde FX-64R is an intelligent addressable fire alarm control panel with one Class A or Class B SLC loop supporting up to 64 addressable devices in any combination of detectors and modules. Two onboard NACs provide 3.75 A total notification power and may be wired as Class B circuits or converted to Class A with the optional SA-CLA module. The panel operates from 120 VAC, provides two 27.4 V DC auxiliary outputs at 500 mA each, supports up to eight remote annunciators, and does not include a dialer.
This part replaces the FX-64RD, with this panel the FX-64R + SA-DACT
Model Variants:
FX-64R = Complete 64-point panel, no dialer
FX-64RD = Complete 64-point panel with dual-line dialer included (Discontinued)
FX-64-RE = Replacement electronics with one 64-point loop
Key Specifications:
Type: Intelligent addressable FACP
Point Capacity: 64 addressable devices
SLC Loops: 1 Class A/B
NAC Circuits: 2 Class B or Class A with SA-CLA, 2.5 A per circuit, 3.75 A total
Primary Power: 120 VAC 60 Hz, 1.3 A max
Accessory Power: Two 27.4 V DC auxiliary outputs, 500 mA each
Battery Support: Two 10 Ah internal, 26 Ah charging capacity
Communicator: Optional SA-DACT dual-line dialer/modem (Contact ID)
Compatible Modules & Accessories:
SA-DACT - Dual-line dialer/modem option card
SA-ETH - Ethernet interface
SA-232 - RS-232 printer/computer interface
SA-CLA - Class A NAC adapter
CTM - City-tie module
BC-1R - 24 Ah battery cabinet
MFC-A - Multifunction auxiliary cabinet
Compatible Detectors & Devices:
KI-OSD - Optical smoke detector
KI-OSHD - Optical smoke / fixed-temperature heat detector
KI-OSCD - Optical smoke + CO detector
KI-HRD - Rate-of-rise heat detector
KI-HFD - Fixed-temperature heat detector
KI-HCD - Heat + CO detector
KIR-OSD - Optical smoke detector with rotary addressing
KIR-HD - Fixed-temperature / rate-of-rise heat detector with rotary addressing
KIR-HCD - Heat + CO detector with rotary addressing
KI-SB - Standard base
KI-IB - Isolator base
KI-RB - Relay base
KI-ABST - Sounder base
FX-270 - Single-action addressable pull station
FX-278 - Dual-action addressable pull station
Compatible for use with:
-
Kidde FX-PD Intelligent Addressable Photoelectric Smoke Detector Head$100.00Condition: NewOut of stock -
Kidde KI-SB4 Standard Detector Mounting Base w/ 4-inch Trim Skirt$15.00Condition: NewOut of stock